Single Phase

KEW-Voltage Monitor Relays (Self Powered)

Features of KEW-AVM-IP:

  • Display: 3-digit Red Seven Segment LED
  • Accuracy: RMS Measurement for precise voltage detection
  • Protection Features: Under / Over Voltage, Single Phase Prevention
  • Power Supply: Wide Range SMPS Power Supply (Self powered version available)

Specification of Voltage Monitor Relay

  • PARAMETER (Voltage): – RY (Phase-Phase)
    – YB (Phase-Phase)
    – BR (Phase-Phase)
    – Average (Phase-Phase)
    – RN (Phase-Neutral)
    – YN (Phase-Neutral)
    – BN (Phase-Neutral)
    – Average (Phase-Neutral)
  • Relay Contact :
    2NOS-8 AMPS, 250VAC POTENTIAL FREE
  • Frequency Trip
    setting:
    45 to 65 Hz
  • VA Burden:
    Auxiliary Supply: <2.5 VA
    Voltage Input: <0.2 VA/Phase
  • Voltage Trip
    setting:
    160–300VAC(L-N), 260-520VAC(L-L)
  • Display: 1 Rows of 3 Digit Red Seven Segment
  • Indications: Error Code Display, Fault LED Indicators
  • Mounting Type: Panel Mount
  • Faceplate: Polycarbonate Transparent
  • Case/Housing Material: FR-ABS Black
  • Connectors/Terminal: Nylon 666, 33%GF
  • Mounting Clamps: Sturdy, Moulded Glass filled nylon with screws
  • Panel
    Dimensions:
    95×35, Depth (Behind Bezel)-65
  • Working Temperature: 0°C to 50°C
  • Storage Temperature: -10°C to 60°C
  • IEC62052-11

Panel Cutout Dimensions

Terminal Connection

Applications and Industries where it is used

Building Management Systems (BMS)

  • Where: In BMS-controlled electrical panels managing HVAC compressors, chilled water pumps, air-handling units, and escalator motors.

  • Why: To monitor supply voltage for overvoltage, undervoltage, or phase loss and signal the BMS to trigger alarms or shut down affected equipment before these conditions cause overheating, efficiency loss, or motor damage — ensuring equipment protection, operational safety, and reduced maintenance interventions.

Motor Control Panels

  • Where: In motor control panels for pumps, compressors, conveyors, and fans, typically installed upstream of the motor starter.

  • Why: To continuously monitor the supply voltage for conditions like overvoltage, undervoltage, or phase loss, and trip the control circuit before these anomalies damage motor windings, cause overheating, or disrupt operations — ensuring motor protection, process reliability, and reduced unplanned downtime.

OEM Electrical Panels

  • Where: In OEM-manufactured electrical panels for machinery like industrial chillers, elevators, packaging machines, and CNC systems, typically installed at the incoming supply point.

  • Why: To monitor incoming voltage for overvoltage, undervoltage, or phase loss and trigger alarms or system shutdown before abnormal supply conditions damage motors, drives, or sensitive control electronics — ensuring machine reliability, reduced warranty claims, and extended service life of customer equipment.

Commercial Sub Metering / Retail Malls

  • Where: In commercial submetering panels and retail mall tenant distribution boards supplying power to shops, food courts, escalators, and common-area facilities.

  • Why: To monitor incoming supply voltage for overvoltage, undervoltage, or phase loss and trigger alarms or disconnect circuits before these conditions damage lighting systems, HVAC units, or tenant equipment — ensuring power quality, equipment longevity, and uninterrupted operation in high-traffic commercial spaces.

     

Ordering Information

Model Accuracy Class Display & Protection Aux Supply
KEW-CMR (SFL-964D) 0.5
1.0
VOLTAGE (L–L & LN) UNDER–OVER SPP VOLTAGE IMBALLANCE 200-600V AC(L-L)
45–270V AC/DC(L-N)
19–60V AC/DC
SELF POWERED
KEW-CMR(SFL-964D+) 0.5
1.0
VOLTAGE (L–L & LN) UNDER–OVER SPP VOLTAGE IMBALLANCE 200-600V AC(L-L)
45–270V AC/DC(L-N)
19–60V AC/DC
SELF POWERED