Single Phase

Three Phase

KEW-AC Single Source Energy Meter

Features of KEW-AVM-IP:

  • Display: 1-row, 6-digit bright LED display
  • Measured Parameters: 1Ø(WAVE-1P-EM): V (L–N), A, W, VA, VAR, PF, Hz, kWh, kVAh 3Ø(WAVE-3P-EM): V (L–N, L–L), A (I₁–I₃), W, VA, VAR, PF (avg & phase), Hz, kWh, kVAh
  • Flexible Integration: RS-485 & MODBUS RTU (optional), programmable CT/PT ratios,
    multi-range auxiliary input
  • Accuracy: ±0.5% for Voltage, Current, Power, and Energy
  • Size: 96×96

Specification of AC Single Source Energy Meter

  • Auxiliary Supply: 150-300V AC, 45-270V AC/DC, 19-60V AC/DC
  • CT / PT Ratio Programmability:
    ▪ PT: Up to 500 kV (Primary), 60–600 V (Secondary)
    ▪ CT: Up to 50kA (Primary), 0.5–5A (Secondary)
  • Accuracy: ±0.5% for Voltage, Current, Power, and Energy
  • VA Burden:
    Auxiliary Supply: <2.5 VA
    Voltage Input:<0.2 VA/Phase
    Current Input: <0.2 VA/Phase
  • Details of
    Parameter’s
    Measured :
    RMS Voltage (20–600V AC)
    RMS Current (0.020–10.00A AC)
    Active Power (0.030–6.000 kW)
    Power Factor (0.3 Lag – 1.0 – 0.3 Lead)
    Frequency (45.00–65.00 Hz)
    Active Energy (0–999999.99 kWh)
    Apparent Energy (0–999999.99 kVAh)
  • Maximum Overload at Input Measurement Side: Voltage
    1.2 Times Continuous
  • Impulse Withstand: 3.5KV for 1.2/50 micro second
  • Display: 1-Row, 6-Digit Bright Red LED Display
  • Digit Height: 0.56”/14.2mm
  • Display Stability: With in +-1 Digit
  • Decimal Point: Auto Scrolling and Manual
  • Refresh Rate: Per 8.0ms
  • Mounting Type: Panel Mount
  • Faceplate: Polycarbonate Transparent
  • Case/Housing Material: FR-ABS Black
  • Connectors/Terminal: Nylon 666, 33%GF
  • Mounting Clamps: Sturdy, Moulded Glass filled nylon with screws
  • Working Temperature: 0°C to 60°C
  • Storage Temperature: –10°C to 70°C
  • IEC62052-11

Panel Cutout Dimensions

Terminal Connection

Applications and Industries where it is used

Electrical Panel

  • Where: AC single source energy meters are used in main LT panels and individual distribution panels to measure total energy consumption from a single incoming power supply.
  • Why: To track energy usage accurately for load monitoring, billing, and energy efficiency management.

Building Management Systems (BMS)

  • Where: AC single source energy meters are used in BMS panels to measure energy consumption of building utilities like HVAC, lighting, and elevators from a single power source.

  • Why: To monitor and manage energy usage, enable cost allocation, and support energy-saving strategies in building operations.

Generator / DG Set Panels

  • Where: AC single source energy meters are used on the output side of Generator / DG Set panels to measure total energy supplied by the generator.

  • Why: To track generator energy output for fuel efficiency analysis, usage monitoring, and accurate operational cost assessment.

Commercial Sub Metering / Retail Malls

  • Where: AC single source energy meters are used in individual tenant panels and common area panels of retail malls to measure energy consumption from a single supply line.

  • Why: To enable accurate tenant-wise energy billing, monitor usage trends, and promote efficient power management.

Ordering Information

Model Parameters Displayed Accuracy Aux Supply Dimensions (MM)
ACEM-BG-1kWh (96×96) Voltage (L-N), Current, Frequency (Class 0.2),
Power Factor (Class 0.5), Active Energy (kWh),
Apparent Energy (kVAh),
Active Power(W), Load Hours
0.5
1.0
45–270V AC/DC
19–60V AC/DC
150–300V AC
96×96
Model Parameters Displayed Accuracy Aux Supply Dimensions (MM)
ACEM-BG-1lWh (96×96)
Voltage (L-N / L-L), Current, Frequency (Class 0.2), Power Factor (Class 0.5), Active Energy (kWh), Active Power (W), Apparent Energy (kVAh), Load Hours
0.5 / 1.0

45–270V AC/DC
19–60V AC/DC
150–300V AC

96×96