KEW-AC Watt and Kilowatt Meter

Features of KEW-AVM-IP:

  • Display: 7-Segment 4-Digit LED Display
  • Measured Parameters:
    • Active Power (W), Active Power (kW), Active Energy (Wh), Active
      Energy (kWh), kW Max Demand
  • Flexible Integration: Optional RS-485 MODBUS RTU Communication, programmable CT/PT ratios, password protection, multiple auxiliary supply options (150-300V AC / 45-270V AC-DC / 19-60V AC-DC)
  • Accuracy: ±0.5% for Voltage, Current, Power
  • Size: 96×96

Specification of AC Watt and Kilowatt Meter

  • Auxiliary Supply: 150–300V AC / 45–270V AC/DC / 19–60V AC/DC
  • Input Range:
    • Input Voltage: 0–600V AC (Direct)
    Input Current: 0.020–10A AC (Direct)
  • Accuracy: ±0.5% for Voltage, Current, Power
  • VA Burden:
    Auxiliary: < 1.5VA
    Voltage Input: <1.0VA
    Current Input: ≤1.0 VA 
  • Input CT/PT
    Programable
    Range: CT Primary: 1A to 50kA AC
    CT Secondary: 0.5A to 5A AC
    PT Primary: 50 to 500kV AC (Programmable in WAVE 3KW)
    PT Secondary: 50 to 500V AC (Programmable in WAVE 3KW)
  • Impulse Withstand: 3.5KV for 1.2/50 micro second
  • Display: 4 Digit 7 Seg RED LED Display(3 Rows)
  • Digit Height: 0.56”/14.2mm
  • Mounting Type: Panel Mount
  • Faceplate: Polycarbonate Transparent
  • Case/Housing Material: FR-ABS Black
  • Connectors/Terminal: Nylon 666, 33%GF
  • Mounting Clamps: Sturdy, Moulded Glass filled nylon with screws
  • Working Temperature: 0°C to 60°C
  • Storage Temperature: –10°C to 70°C
  • IEC62052-11

Panel Cutout Dimensions

Terminal Connection

Applications and Industries where it is used

Electrical Panel

  • Where: Watt and kilowatt meters are used in main LT panels and distribution panels to measure active power consumption of connected electrical loads.
  • Why: To monitor real-time power usage, support energy audits, and optimize load distribution for efficient energy management.

Building Management Systems (BMS)

  • Where: Used in BMS panels to measure the active power consumption of HVAC systems, lighting, and other building services.

  • Why: To track energy usage, enable accurate load profiling, and support efficient energy management and cost control.

Generator / DG Set Panels

  • Where: used on the output side of Generator / DG Set panels to measure the real-time active power delivered to the load.

  • Why: To monitor generator load, prevent overloading, and ensure optimal power generation efficiency.

Commercial Sub Metering / Retail Malls

  • Where: Watt and kilowatt meters are used in individual tenant panels and common area sub-metering panels in retail malls to measure real-time power consumption.

  • Why: To ensure fair energy billing, monitor usage patterns, and support energy efficiency initiatives across different zones or tenants.

Ordering Information

Model Measuring Range Accuracy Aux Supply Dimensions (MM)
ACWM-BG-1W (96×96) Voltage Input: 20–600V AC (Direct)
Current Input: 0.080–10A AC (Direct)
0.020–1A AC (Direct)
0.1A–30A AC(Direct)
0.5 • 150-300V AC (TX Supply)
• 45-270V AC/DC
• 19-60V AC/DC
96×96
Model Measuring Range Accuracy Aux Supply Dimensions (MM)
ACWM-BG-3W (96×96)
Voltage Input: 20–600V (Line to Neutral) 30–1000V (Line to Line) Current Input: 0.020–10A AC 0.1A–30A Direct AC CT Operated
0.5
• 45-270V AC/DC •19-60V AC/DC
96×96